Hacking of Cooling Systems in Approximately 700 French Stores Reveals the Risks of Exposed Control Devices

Attackers exploited outdated, internet-connected control devices to manage cooling systems in approximately 700 stores in France, damaging large quantities of food and causing fires in some cases. The incident indicates that the lack of updates and failure to isolate access from the internet facilitated a widespread breach.

2026-10-14
3 min read
15 views
certi.news
Hacking of Cooling Systems in Approximately 700 French Stores Reveals the Risks of Exposed Control Devices

A mass breach of cooling systems in approximately 700 supermarket stores in France disrupted refrigerators and freezers, with temperatures inside some of them rising to 50 degrees Celsius. This resulted in damage to unspecified quantities of food and fires in some electrical systems.

The attackers targeted internet-connected control units that allow technicians to manage store cooling systems remotely. After compromising them, they activated defrost functions for extended periods, causing temperatures to rise instead of maintaining the cold chain. Effects linked to the incident were also reported in Spain, Portugal, Poland, Germany and Belgium.

Known vulnerabilities in outdated devices

According to research reports and public security advisories, the affected devices included models from Denmark-based Danfoss, Dixell and its US-based parent company Copeland. Until recently, some models of Danfoss units used a daily password generated based on the date within firmware available for analysis. Because the password was identical across models installed in hundreds or thousands of stores, it could be reproduced on devices that had not received a recent update.

Advertisement

Copeland and Dixell units also contained critical vulnerabilities that were fixed during the past few months, and they allowed remote access with privileges similar to those of administrators. This indicates that the problem was not remote connectivity itself, but operating outdated devices while leaving them accessible from the public internet.

What could practically have been prevented?

Researchers from Pen Test Partners said that basic measures could have changed the outcome of the incident, including removing control units from the public internet, placing remote access behind a VPN and a list of permitted IP addresses, changing known or default credentials, and updating the software to current versions.

The researchers also stressed the need to bring third-party equipment onto the organization’s network in a documented manner and under its control, rather than leaving it connected through a connection belonging to an external contractor. Claroty had warned of the risks of ignoring these measures last October, while the US Cybersecurity and Infrastructure Security Agency, CISA, issued a similar warning in February.

The responsible party and unanswered lessons

The party behind the attack has not claimed responsibility, so its motives remain unresolved between large-scale sabotage and the possibility that an international or government actor carried out a cross-border disruption operation. Copeland acknowledged a vulnerability in a discontinued and end-of-support generation of control units and said it was working with customers to prevent similar incidents. Danfoss did not immediately respond to Ars Technica’s questions, with discontinued models also having been part of the discussion.

The incident is significant because it illustrates how a small industrial device, if managed with outdated software and exposed access, can become a point of direct operational impact on inventory and facility safety. However, the source does not determine the number of compromised devices or the final value of the losses, nor does it establish the attacker’s identity or motive so far.

News source
c
Author

certi.news

What you need to know

Old, internet-exposed controllers were used to manipulate refrigeration systems in approximately 700 French stores, causing food spoilage and, in some cases, fires. The incident highlights the importance of updating devices, changing passwords, and isolating access from the public internet using measures such as VPNs and allowlisted IP addresses.

  • The attackers targeted internet-connected controllers used to manage refrigeration systems remotely.
  • Running defrost functions for extended periods caused temperatures inside some stores to rise to as high as 50°C.
  • Affected devices included models from Danfoss, Dixell, and Copeland, some of which were old or no longer supported.
  • Some Danfoss controllers used a reproducible daily password based on the date embedded in the firmware.
  • Vulnerabilities in Copeland and Dixell controllers included remote access with privileges similar to those of administrators.
  • Researchers recommended removing the devices from the public internet, using VPNs and allowlisted IP addresses, updating software, and changing credentials.

FAQ

How many stores were affected by the hack?

Approximately 700 supermarket stores in France were affected, with incident-related impacts also reported in Spain, Portugal, Poland, Germany, and Belgium.

How did the hack cause food spoilage?

The attackers ran defrost functions for extended periods, causing temperatures inside refrigerators and freezers to rise and breaking the cold chain.

What measures could have prevented the incident?

Recommended measures included isolating the controllers from the public internet, placing remote access behind a VPN and an allowlisted IP address, changing passwords, and updating software.

Was the party responsible for the attack identified?

No. No group has claimed responsibility, and the attackers’ motives and identity remain unresolved.